The Siemens HJD62B200 is a 200-amp, 2-pole, 600VAC Sentron series JD-frame molded case circuit breaker with high interrupting capacity. The HJD6 type designation indicates the JD frame (400A frame) with high interrupting (H) rating — 100kA at 240V, 65kA at 480V, and 35kA at 600V. The HJD62B200 is the 2-pole variant of the JD frame family, used in commercial and industrial applications requiring high fault current interruption. The JD frame is a large-frame breaker (400A frame) available from 200A to 400A, making it suitable for feeder and main circuit protection in switchboards and panelboards. Interchangeable trip units are available for the JD frame. Dimensions: 11" L x 7.5" W x 4" D.
| Specification | Value |
|---|---|
| Amperage | 200A |
| Poles | 2 |
| Voltage | 600VAC / 500VDC |
| Interrupt Rating | 100kA @ 240V · 65kA @ 480V · 35kA @ 600V |
| Frame Size | JD Frame (400A Frame) |
| Mounting Type | Bolt-On |
| Trip Type | Thermal Magnetic |
| Trip Function | LI — Long-Time, Instantaneous |
| Wire Size | #3/0–500 kcmil Cu/Al (with TA2J6500 lug) |
| Phase | 2-Phase |
| Standards | UL 489, IEC 60947-2 |
| Temperature Rating | 40°C |
Siemens Sentron HJD6 JD-Frame 200A 2-pole circuit breaker. In stock at AllBreakerSales.com. Call (877) 611-0034 for same-day pricing. Genuine OEM parts, ships from US warehouse.
Brand: Siemens | Series: Sentron HJD6 JD-Frame | Catalog Number: HJD62B200
HJD62B225 - Siemens Sentron HJD6 JD-Frame | HJD62B250 - Siemens Sentron HJD6 JD-Frame | HJD63B200 - Siemens HJD High-AIC J-Frame | HJD63B225 - Siemens HJD High-AIC J-Frame | HJD63B250 - Siemens HJD High-AIC J-Frame